🔌

Electrical Power Balance

Free

List your equipment, apply simultaneity factors and size your main switchboard.

Equipment
kW

Simultaneity

kW

Simultaneity

kW

Simultaneity

kW

Simultaneity

kW

Simultaneity

⚙️Parameters
%

Future expansion

📊Power assessment

🔌Installed P

142kW

Utilised P (Ku)

73,85kW

📈P with reserve

88,62kW

🔋Apparent power

105,28kVA

Rated current

152A

🔧MSB rating

160A

Recommended subscribed power

108kVA

Weighted average cos φ

0,84

Breakdown by item

LED lighting2.0 kW inst.1.6 kW util.
Desktop PC + monitor15.0 kW inst.10.5 kW util.
Split AC25.0 kW inst.18.8 kW util.
Socket outlets (per circuit)70.0 kW inst.28.0 kW util.
Lift30.0 kW inst.15.0 kW util.
📐 Formulas
P_installée = Σ(P_unit × Qté) P_utilisée = Σ(P_installée × Ks) S_apparente = P_utilisée / cos φ I = P / (√3 × U × cos φ)

Ks = simultaneity factor (not all equipment runs at once). Power reserve covers future extensions.

Standards & regulations

  • NF C 15-100Installations électriques à basse tension
  • NF C 14-100Installations de branchement (ENEDIS)
  • UTE C 15-105Guide pratique — Détermination des sections de conducteurs

This tool provides indicative estimates. Results do not substitute professional advice. Always verify with current regulations.

Related sector guides

Responding to a public tender?

Generate your technical memorandum with sector expertise enabled.

Generate a technical memorandum